A. POINT
  WIRING SYSTEM
 | 
 
  | 1. All
  Wall / Slab Concealed conduit shall be PVC heavy -Duty conduit & surface
  conduit shall be FRLS PVC Type | 
 
  | 2. All
  PVC conduits shall be jointed by slip type of socket with approved sealing
  cement. | 
 
  | 3. PVC
  Conduits upto 32mm dia shall be 1.8mm wall thickness and above that shall be
  2.2mm wall thickness. | 
 
  | 4. 1.5mm
  thick GI saddles and grouting the same for exposed conduit work. | 
 
  | 5. 1.8
  mm thick GI MK Outlet boxes and junction box | 
 
  | 6. 8.3
  mm thick cable gland plates shall be provided on top as well as at the bottom
  of the GI MK Outlet box / panel. | 
 
  | 7. All
  sockets shall be shuttered type with earth terminal. | 
 
   | 
 
  
B. CABLE
  & CONTAINMENT
 | 
 
  | 1. The
  numbers of insulated wires that may be drawn in the conduits of various sizes
  and the conduit fill shall not exceed 40%. | 
 
  | 2. FRLS
  PVC insulated copper conductor stranded wire of Green colour with yellow
  bands for earthing of fixtures, outlet boxes & socket. | 
 
  | 3.
  Separate neutral and earthing wire shall be provided for each circuit. | 
 
  | 4.
  Lighting and power circuit to be kept separate. | 
 
  | 5.
  Wherever the cables are of aluminium and bus bars of copper bimetallic lugs
  shall be used. | 
 
   | 
 
  
C. LIGHT
  FIXTURES
 | 
 
  | 1.
  Drilling holes in supports wherever required. | 
 
  | 2.
  Testing of all fixtures before and after installation. | 
 
  | 3. All
  Emergency lighting shall be feed from EDB with 3 hours inverter backup. | 
 
   | 
 
  
D.
  DISTRIBUTION BOARDS
 | 
 
  
 
 
  | 1.
  Cubicle type, 2mm CRCA sheet steel enclosed. | 
  
  | 2. All
  MCB’s shall be of appropriate breaking capacity but minimum of 10 KA breaking
  capacity. | 
  
  | 3.
  MCCB’s shall be appropriate breaking capacity 16A to 160A breaking capacity
  25 KA & 200A to 630A breaking capacity 36 KA & 800A to 1250A breaking
  capacity 50 KA  | 
  
  | 4. All
  MCB’s used for protection of resistive and lightly inductive load shall be
  type “B” characteristic and inductive (motor) load shall be of type “C”
  characteristic and discharge lamps and UPS etc. shall be of type D
  characteristic.  | 
  
  | 5. The
  breaking capacity of MCCB’s are mentioned panel wise. Up to 250A MCCB’s shall
  be with thermal magnetic releases and above rating MCCB's shall be with
  microprocessor based. | 
  
  | 6.
  Distribution panels shall be Powder Coated with Siemens grey paint . | 
  
  | 7. All
  hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. | 
  
 
 | 
   | 
 
  
E.
  EARTHING INSTALLATION
 | 
 
  | 1. All
  earthing pits shall be interconnected. | 
 
  | 2. All
  DBs, panels to be connected on earthing with suitable strip / wires | 
 
 